Location: ¡ÏPLC¡ÏProduct Information ¡ÏSR Product Type ¡ÏSR-20ERA
 
 
¡ö This intelligent controller, adopting function block programming, having large programming capacity, being f reely
  fprogrammed according to different users and different fields, can run at your desired time table and the RTC
  accuracy can reach second and makes your time control more accurate. And up to 128 time sessions can
 

be set , especially suitable for time-control system.

¡ö Safety password function makes your program absolutely safe. Before writing program, password can be set. And only
  after entering the correct password, can the program be modified.
¡ö It is equipped with a removable, convenient and programmable LCD, providing 64 friendly human-machine interfaces,
  32 virtual keys, having the function to display the alarming message and parameter and to modify the parameter.
  When needed, it can be installed. And when not needed, it can be removed and replaced with an ordinary front panel.
  Thus the cost will be greatly reduced.
¡ö The input can receive not only the digital input but also the analogue input to perform the control and . transmission of
 

fthe temperature, moisture, pressure, flow level unit and so on.

¡ö It has well-featured and compact design with 12 point input and 8 point output. Equipped with expansion module, it can
  be expanded into 82 I/O better ,and to MAX 122I/O.It can be connected with telephone voice module and remote control
  module to perform the notification and alarming function. And the connection between the host and the module can
  be Bridge SR-CBA or flexible connection SR-ECBA.
¡ö The machine has short-circuit protection (internal) and relay output protection (external) function, which makes your
usage safer and easier.
   
 
Power supply
Power
AC110V-240V
Input parameters:
Input No
12(X0-A7,Y0-Y3)
Digital input
12(X0-A7,Y0-Y3)
Analogue input
None
Power range
AC0-240V
Input signal0
AC0-40V
Input signal1
AC85-240V
Output parameters:
Output No
8(QX0-QX7)
Output type
Relay output
Output voltage
AC0-240V/DC0-24V
Output current
Resistive load 10A/Inductive load 2A
Environment temperature:
Running temperature
0¡æ¡«55¡æ
Storage/shipment
-40¡æ¡«70¡æ
Switch frequency:
Mechanism
10Hz
Resistor/light load
2Hz
Sensitive load
0.5Hz
Other parameters:
Clock buffer memory at 25¡æ
80h
RTC accuracy
Max¡À5s/day

Protection

IP20
Emission on line
EN55011(B)
The main frequency range
47-63Hz
Function block No
128¸ö
Program storage capacity
64K
Isolation intensity
IEC1131